fig-3

IBC Code sections

Figure 3. Table 506.2 (top) limits the allowable area for non-sprinklered Type IIA libraries (Group A-3) to 15,500 sq.ft; but Section 903.2.1.3 (bottom) limits Group A-3 fire areas to 12,000 sq.ft. Taken together, Section 903.2.1.3 places a limit on the application of Table 506.2, but does not contradict it.

IBC Code sections